The DC Line Monitor measures DC voltage and reports DC current measured with attached Hall-Effect transducers (sold separately) to the ENVIROMUX-2D/5D/16D unit.
Environment Monitoring System AC & DC Power Monitors
Power Relays & Sensors compatible with E-2D, E-5D and E-16D
Compatible with E-FSC Fiber Converter/Extender.
- Use to extend sensor up to 1.2 miles (2km) from the ENVIROMUX unit.
For more information, visit http://www.networktechinc.com/ac-power-monitor.html
- Reports DC voltage and DC current. Current measurements require Hall-Effect transducers (sold separately). Polling rate: 1Sa/s.
- Six 2-pin terminal blocks for measuring DC voltage Non-isolated -60 to +60V DC 0.12VDC resolution 1.2VDC accuracy
- Six non-rectifying Hall Effect 4-pin transducer interfaces for measuring DC current 0.2% resolution Accuracy and range are transducer-dependent (sold separately).
- Supports CAT5/5e/6 cable up to 1,000 ft (305 m) (18-24 AWG).
- Current consumption: 190mA @ 12VDC.
- Powered by E-2D/5D/16D. The E-DCLM-6 may require more power than the RJ45 sensor ports can supply on the E-2D/15D/16D. Refer to page 2 of the manual to determine if the optional PWR-SPLY-12V1A power supply is necessary for you